Application – Cleanroom supply- and return air, fan filter units, cleanroom gel ceilingType – EPA-HEPA and ULPA panel with a knifeEdge fot Gel Seal sealing and fan filter unitsMedia – Waterproof micro glass fibersGasket – None or 2 component polyurethane one piece endless sealSeperator – Thermoplastic hotmeltFaceguard – Mild steel epoxy coatedFilter classification – E11 – U17Nominal airflow – 0,45 m/sAir volume – up till 2700 m3/hInitial pressure drop – 70 – 165 PaTemperature max – 70 °C in continuous operationFiltertest – EN1822;2010 |